Description
Air Inverter II - B is the new heat pump with wall installable for heating, cooling and DHW production.
It is composed of an external unit with very high efficiency and a small box for the interior. Air Inverter II - B can be installed on the wall and in any building minimizing space and optimizing architectural integration building.
It is available in 7 sizes from 4kW to 16kW with single-phase and three-phase power supply. It works with wide operating limits from -20 ° C to 46 ° C outside and with delivery temperatures up to 60 ° C.
It is suitable both in new buildings and in the case of energy requalification in a single or multi-family residential area.
Get more information about your email
The compact heat pump
The Air Inverter II - B heat pump consists of two sections:
- An internal unit of compact dimensions, which can be fixed to the wall, designed for direct connection to a sanitary storage tank.
- The silent outdoor unit with extremely small dimensions.
The advantage of the heat pump is its small size, it can be easily installed instead of the old wall-mounted boiler or in the kitchen cupboards.

Internal unit structure
1) Load-bearing structure in highly resistant sheet metal
2) Hydronic module
3) Supplementary electric heater from 2-4 kW and 6 kW (optional)
4) 3 valve through pre-wired sanitary management
5) 3 bar safety valve with pressure gauge
6) Condensate collection tray
Receive information and documentation on your email now
The heat pump is easy to install
Air Inverter II B meets the needs of every type of residential building with a decentralized system.
They have been designed to speed up the installation phases, as the indoor unit contains the main components needed for the plumbing and heating system.
Air Inverter II - B adapts perfectly to systems with radiant panels, fan coils, storage tanks for domestic hot water.
Features and Models
Model |
Pot fridge * |
EER |
Pot term. |
COP |
Nutrition |
Energy efficiency class |
|
|
|
|
|
|
MT - BT |
04 M |
4,47 kW |
5,58 |
4,23 kW |
5,21 |
230 / 1 / V 50 |
A ++ | A ++ |
06 M |
6,19 kW |
4,80 |
6,33 kW |
4,83 |
230 / 1 / V 50 |
A ++ | A ++ |
08 M |
8,01 kW |
4,43 |
8,09 kW |
4,57 |
230 / 1 / V 50 |
A ++ | A ++ |
12 M |
11,4 kW |
4,40 |
12,2 kW |
4,79 |
230 / 1 / V 50 |
A ++ | A ++ |
12 T |
11,4 kW |
4,40 |
12,2 kW |
4,79 |
400 / 3 / V 50 |
A ++ | A ++ |
16 M |
15,4 kW |
4,33 |
15,8 kW |
4,81 |
230 / 1 / V 50 |
A + | A ++ |
16 T |
15,4 kW |
4,33 |
15,8 kW |
4,81 |
400 / 3 / V 50 |
A + | A ++ |
Terms of reference:
Cooling: A35 / W18
Heating: A7 / W35 (EN 14511)
Fill out the form for a quote or information
Design
Technical data Air Inverter II - B
Features and Models
SIZES |
UM |
04M |
06M |
08M |
12M / T |
16M / T |
VERSIONS |
|
IN-TB |
IN-TB |
IN-TB |
TB |
TB |
HEATING Inlet / outlet water use side 30 / 35 ° C - Source side air 7 ° C (UR = 85%) |
Thermal power |
kW |
4,23 |
6,33 |
8,09 |
12,16 |
15,77 |
Total input |
kW |
0,81 |
1,31 |
1,77 |
2,54 |
3,28 |
COP |
- |
5,21 |
4,83 |
4,57 |
4,79 |
4,81 |
Water flow |
l / s |
0,20 |
0,30 |
0,39 |
0,56 |
0,74 |
Maximum useful prevalence |
kPa |
71,0 |
63,0 |
55,0 |
78,0 |
54,0 |
HEATING Inlet / outlet water use side 30 / 35 ° C - Source side air 7 ° C (UR = 85%) |
Thermal power |
kW |
4,78 |
5,68 |
6,09 |
9,76 |
12,06 |
Total input |
kW |
1,56 |
1,95 |
2,18 |
3,32 |
4,14 |
COP |
- |
3,06 |
2,91 |
2,79 |
2,94 |
2,91 |
Water flow |
l / s |
0,23 |
0,27 |
0,29 |
0,45 |
0,56 |
Maximum useful prevalence |
kPa |
71,0 |
63,0 |
55,0 |
78,0 |
54,0 |
HEATING Inlet / outlet water use side 30 / 35 ° C - Source side air 7 ° C (UR = 85%) |
Thermal power |
kW |
4,06 |
6,00 |
7,29 |
12,22 |
16,44 |
Total input |
kW |
1,10 |
1,65 |
2,15 |
3,35 |
4,42 |
COP |
- |
3,69 |
3,64 |
3,39 |
3,65 |
3,72 |
Water flow |
l / s |
0,19 |
0,29 |
0,35 |
0,57 |
0,77 |
Maximum useful prevalence |
kPa |
72,0 |
65,0 |
53,0 |
82,0 |
62,0 |
COOLING Water inlet / outlet side of use 18 / 23 ° C - Air on source side 35 ° C |
Thermal power |
kW |
4,47 |
6,19 |
8,01 |
11,39 |
15,40 |
Total input |
kW |
0,80 |
1,29 |
1,81 |
2,59 |
3,56 |
COP |
- |
5,58 |
4,80 |
4,43 |
4,40 |
4,33 |
Water flow |
l / s |
0,21 |
0,30 |
0,38 |
0,54 |
0,74 |
Maximum useful prevalence |
kPa |
71,0 |
63,0 |
55,0 |
78,0 |
54,0 |
COOLING Water inlet / outlet side of use 7 / 12 ° C - Air on source side 35 ° C |
Cooling capacity |
kW |
4,34 |
6,24 |
7,57 |
11,34 |
15,53 |
Total input |
kW |
1,27 |
2,05 |
2,73 |
4,25 |
5,71 |
EER |
- |
3,42 |
3,05 |
2,77 |
2,67 |
2,72 |
ESEER |
- |
4,82 |
4,58 |
3,85 |
4,32 |
4,02 |
Water flow |
l / s |
0,21 |
0,30 |
0,36 |
0,54 |
0,74 |
Maximum useful prevalence |
kPa |
71,0 |
63,0 |
55,0 |
78,0 |
54,0 |
Total power consumption and performance according to EN 14511: 2013 |
Operating limits
Cooling, heating and domestic hot water Air Inverter II - T.

Twu (° C): exchanger outlet water temperature
Tae (° C): outdoor air temperature
(1) Normal operating range
(2) Operating range with the use of resistance

ΔP (kPa): useful prevalence
Q (l / s): water flow rate
Pel (W): absorbed electrical power
Dimensional units
DIMENSIONAL INTERNAL UNITS
Size UM 04 M-06 M-08 M 12 - 16 M / T
Weight in operation 48 50 kg
Shipping weight kg 49 51

1 Electrical panel
2 Unit control keypad
3 Power line input
4 Functional spaces standard units
5 Exchange heat exchanger ACS 3 / 4 ”(with VI)
6 Return exchanger ACS 3 / 4 ”(with VI)
7 System delivery side use 3 / 4 ”(with
8 RV.iIt) installation of use side 3 / 4 ”(with VI)
9 Suction attachment 5 / 8 ”
10 Liquid connection 3 / 8 ”
11 Pressure gauge
12 System loading valve
13 1 condensate drain "
14 System vent valve
VI Shut-off valve
DIMENSIONAL EXTERNAL UNIT 04 M - 06M

Size - UM - 04 M - 06 M
Operating weight - kg - 60 - 60
Shipping weight - kg - 72 - 72
1 Compressor compartment
2 Electrical panel
3 Power line input
4 Condensate drain
5 Suction attachment 5 / 8 ”
6 Liquid connection 3 / 8 ”
7 Functional spaces
8 Electric fan
DIMENSIONALS EXTERNAL UNIT 08 M

Size - UM - 08 M
Operating weight - kg - 76
Shipping weight - kg - 88
1 Compressor compartment
2 Electrical panel
3 Power line input
4 Condensate drain
5 Suction attachment 5 / 8 ”
6 Liquid connection 3 / 8 ”
7 Functional spaces
8 Electric fan
DIMENSIONAL EXTERNAL UNIT 12 M / T

Size - UM - 12 M / T - 16M / T
Operating weight - kg - 115 - 115
Shipping weight - kg - 128 - 128
9. Compressor compartment
10. Electrical cabinet
11. Power line entry
12. Condensate drain
13. Liquid line connections
14. Gas line connections
15. Functional spaces
16. electric fan
Video photo