Technical Information
Iris Wall is the wall-mounted fan coil low noise impact able to cover the heating and cooling needs in the sector, commercial and receptive.
Iris Wall fan coils adapt with a completely innovative design to environments where aesthetic, space and silence requirements are the greatest constraint.
Fill out the form to receive more information
Components and performance characteristics
Refined and elegant design
- On-board LCD display for temperature indication
- Available in sizes 3
- Night sleep function, auto-restart system
- Standard control with advanced functions
- Master / slave combination up to 32 units
- Brushless DC fan
- Quick installation thanks to the standard 3 series valves
- Delivery adjustability through motorized deflector
- Easy access to the air filter
- Removable and washable air filter
Innovative design, on-board display
The Iris Wall wall fan coil has a pleasant design that makes it suitable both in the residential sector and in the service and commercial sectors.
Iris Wall comes with a display on the machine for the indication of the temperature, surrounded by LEDs for a quick interpretation of the functions set.
The air supply can be adjusted thanks to the motorized deflector that ensures correct air distribution in the environment, avoiding bothersome direct flows on people.
Simple to install
Iris Wall, thanks to master / slave function, it can be connected in series up to 32 units with the possibility to manage the whole system with a single remote control or wall control.
The whole system is integrated in a single machine, has no external motors and installation is quick and easy thanks to the three-way valves fitted as standard.
The system is easily accessible for maintenance operations.
EC Brushless performing motors
Iris Wall Uses Brushless EC motors, with tangential fans in plastic material. This feature allows a net reduction of the noise level emitted, as well as a reduction in the electrical absorption of the motor, compared to traditional fans with a metal structure.
The EC Brushless electric motors allow you to fine-tune the speed of the fan assembly, limiting the energy supply to the actual workload required without unnecessary waste.
Features and Models
Model |
Refrigerating capacity
|
Thermal Pot
|
air flow |
Water flow |
Iris Wall 25 |
2.39 kW max |
3.13 kW max |
500 m3/h |
427 l / h |
Iris Wall 30 |
3.01 kW max |
3.81 kW max |
645 m3/h |
525 l / h |
Iris Wall 40 |
3.71 kW max |
4.97 kW max |
788 m3/h |
641,91 l / h |
Operating Conditions
Heating: Air 20 ° C - Water inlet 45 ° Cb-b -Water output 40 ° C
Cooling: Air 27 ° C bs 19 ° C / bu-Water 7 ° C / 12 ° C
Planning
Specifications
IRIS data WALL |
um |
25 |
30 |
40 |
Fans |
No. |
1 |
Nutrition |
V / Ph / H |
230/1/50220/1/60 |
electrical data |
Motor |
MAX |
W |
13 |
22 |
30 |
MED |
10 |
15 |
20 |
MIN |
8 |
10 |
15 |
Maximum power |
36 |
52 |
60 |
Maximum current |
A |
0,156 |
0,226 |
0,261 |
Hydraulic data |
Water flow in cooling |
MAX |
L / hr |
411 |
519 |
641 |
MED |
317 |
425 |
562 |
MIN |
278 |
321 |
458 |
Pressure differential |
MAX |
kPa |
27,5 |
38,5 |
50,0 |
MED |
16,6 |
27,5 |
40,0 |
MIN |
13,2 |
15,6 |
28,0 |
Water flow in heating |
MAX |
L / hr |
460 |
561 |
766 |
MED |
358 |
419 |
733 |
MIN |
289 |
358 |
594 |
Pressure differential |
MAX |
kPa |
29,0 |
38,9 |
51,5 |
MED |
17,8 |
27,6 |
46,4 |
MIN |
12,8 |
16,5 |
32,1 |
water content |
L |
0,124 |
0,124 |
0,192 |
Hydraulic connections and packaging |
Hydraulic connections |
|
Market |
Connector (female thread) |
IN |
inch |
½ " |
O |
Condensate drain |
mm |
16 |
Dimensions: |
L |
mm |
876 |
W |
228 |
H |
300 |
Net weight |
kg |
13 |
13 |
14 |
Structure
Front shell and back in ABS plastic material. Two flexible hoses are supplied as standard for the hydraulic connection.
The color is RAL 9010 pure white.
Control
Obtained through infrared remote control. Includes: three-way valve control, status indication for the chiller or boiler, auto-restart, automatic flap oscillation and cool-heat-ventilation-timersleep functions.
The software for units with valve or without valve is already included in the machine together with the master slave function.
Fan group
Consisting of a tangential fan and electric motor directly coupled with three rotation speeds.
Heat exchange coil
It is made up of internally turbulent copper pipes to increase the efficiency of the exchange, and of a continuous pack of aluminum fins.
ACCESSORIES:
- Condensate drain pump to be installed outside the unit. It is supplied separately.
- Wall control via telephone cable (alternative to remote control).
- Data logger for connection to BMS communication network with Modbus protocol.
- Data logger for max. 32 units, max. 64 data loggers. Total max. 2048 units per network
Dimensional Iris Wall

Dimensions: |
UM |
25 |
30 |
40 |
A |
mm |
876 |
876 |
876 |
B |
mm |
300 |
300 |
300 |
C |
mm |
228 |
228 |
228 |
Weight |
kg |
13 |
13 |
14 |
Installation
Choose the installation wall
Select the installation location of the wall unit by taking the following considerations:
- to. The front of the air inlet and outlet must be free of obstacles. The air must flow freely.
- b. The wall where the unit must be installed must be solid and insulated so as not to transmit noise.
- c. The position must allow easy installation of the supply and drainage water pipes.
- d. Make sure that the space around the fan coil complies with the indications in the following drawing.
- is. From the floor the unit should be installed at least above eye level.
- f. Avoid installing the unit exposed to direct sunlight.

Networking
Master unit function
The master unit sends data on its setting to the slave units. The settings of the master unit are:
ON / OFF unit, fan speed mode, temperature, swing and sleep function for remote control operation.
The settings of the master unit are: ON / OFF unit, fan speed mode, set temperature, Swing function, sleep and weekly ON / OFF timer program for operation from keypad to wall.
Slave unit function
The slave unit receives data on its master unit settings.
The slave unit is allowed to change to a locally desired setting, as long as there are no subsequent changes to the master unit settings.
Slave units can be individually set for Mode function, fan speed, set temperature, weekly programmable timer (via wall keypad operation), sleep function and flap function.
Schemes
Example of a system:
The wall-mounted fan coil is used for heating, it is connected to the heat pump that also manages the production of domestic hot water.
1 Iris Wall fan coil
2 pumping groups
3 accumulation
4 instant hot water station
5 heat pump
Video photo
Iris Wall fan coils images