Technical Information

ECOFLOOR slim is the radiant system for the low-floor heating and winter and summer air conditioning of the rooms.
The ECOfloor Slim radiant panels have a thickness of only 18 mm which makes the system particularly suitable for application on existing floors. ECOfloor Slim is quick and easy to install and allows you to improve construction site logistics.
The lowered floor radiant system, in addition to being an excellent heating system for the winter, is also the solution for summer cooling. With a single system, low consumption and invisible, it is possible to obtain comfort and savings in all seasons.

Technical features
- Special plaster fiber flooring
- Fire resistance, class E
- Moisture barrier according to UNI EN 1264-4
- Interlocking for easy connection of several modules
- Resistant to high temperature deformation (80 ° C)
- Certificates according to green building guidelines
- Joggles tube holder with the possibility of variable pitch
- High resistance to wear and foot traffic
- Thickness ideal content for low profile systems.
The installation of the panels can be performed fast and accurate thanks to the additional optional accessories for proper installation. The compact structure dell'ECOfloor slim allows the realization of a plant floor radiant even with little thickness available.

Fast heating and cooling
ECOfloor Slim occupies only 21 mm thick, Excluding the floor and additional insulation.
In addition to the great advantage of the low thickness of the system, the absence of traditional screed gives the system ECOFLOOR Slim a reduced thermal inertia.
This ensures a faster response to the adjustment, both in heating and cooling, and a more rapid operation of the system.
The result is more comfort more quickly.

Saves on time and costs on site
The construction of a plant may be low at first glance more expensive than a standard radiant system.
In fact, the structure of ECOFLOOR Slim with dry screed provides a huge cost savings in construction.
The realization of the traditional screed, in fact, involves long lead times and increased investment in terms of people, resources and costs, without excluding any issues related to the installation.
Moreover, the drying of the screed can require more than three weeks, resulting in longer waiting for the customer.
Where can I install the low-floor system
ECOFLOOR Slim integrates into any architectural environment, from new buildings to renovations, for all sectors such as residential, public buildings, offices and service sectors.
Installation in new buildings
ECOFLOOR Slim is being used in all those applications where loads are required and space is limited.
Buildings under renovation:
The thickness of only 21 mm (excluding floor), making it particularly suitable for ECOFLOOR Slim restructuring accomplishments in lofts or on existing floors.
modular panels, lightweight and easy to install
The special Ecofloor Slim panels are made from a layer of plaster fiber with a thickness of 18 mm milled for housing the hydraulic circuits. To cover the entire surface of the floor, the panels are available in different formats, which can be combined with each other:
Panels with milling characterized by a linear geometry specially designed to enable the drafting of the coils at the same time, with a linear and curvilinear, and easy connection to the supply lines.
Panels with indented milling, are available in two versions with step 100 50 mm and mm: this last is particularly useful in the adduction areas near the manifold, such as in lobbies and hallways, where it is necessary to stay in a small space many tubes of connection to different environments.
The other components of the system
Tube high strength
The PE-RT pipe is a pipe 12 mm ideally plastic surfaces for radiant systems.
The inner tube is made with a special PE-RT is resistant to high temperatures.

Connection fittings
The special Y-joint allows you to connect to each output from the collector two circuits radians.
The use of joints can reduce installation costs and at the same time the dimensions of the manifold, while maintaining the functionality of the system.

Distribution manifold
The newly designed modular manifold, with variable number of outlets from 2 to 18, is connected to the hydraulic circuit, thanks to special push-button fittings and without the need for special tools. System calibration is extremely simplified thanks to the graduated scale on the individual delivery flowmeters.
Cassette collectors
The mounting box is designed to position with ease the distribution manifolds of the radiant systems. Includes Mounting rails collectors and height adjustable feet.
Banda perimeter insulation
The band in polyethylene, placed between walls and the radiant panels, has the function to absorb the expansion of the screed and to obtain a good thermal and acoustic insulation. It 'made of special materials that make it resistant to mold.

Products for finishing
To complete the system a range of accessories and materials required for the proper installation. As the adhesive sealant PU 45 in cartridges, the primer M for existing floors and the powder mixture for finishing leveling.
Planning
ECOfloor Slim is the radiant system in plasterboard panels of only 18 mm for the construction of ultra-low-profile dry floors. ECOfloor Silm panels are pre-shaped to house hydraulic circuits and can be equipped with insulating plates on the underside. The hydraulic circuits with PE-RT multilayer pipe with 12x1,3 mm diameter are placed directly in the traces of the panels to form the radiant coils. The reduced thickness of the radiant system gives it a reduced thermal inertia, guaranteeing a quicker set-up and a faster response to regulation, both in heating and cooling.
Composition
1) Polyester Foam Synthesized 10 mm
2) pipe PE-RT 12x1.3 mm
3) Panel plaster fiber 18 mm
4) layer of leveling or self-leveling
5) Floor
As is composed ECOFLOOR Slim
To simplify the installation of the lowered system, we have created 4 types of panels, which can be combined together.
Milling linear

Its structure allows both the drafting of the coils, with linear and curvilinear development, and both the passage of the feeding lines.
|
Milling rusticated

With 50 and 100mm pitch useful near the manifold, and in rooms and corridors, where it is necessary to connect numerous pipes in a small space.
|
For collectors

The short distance between the studs can accommodate a large number of tubes (up to 40) without overlapping or sharp bends.
|
Additional insulating

Is available upon request to have an additional layer of EPS insulation directly coupled to the underside.
|
Specifications gypsum fiber panels ECOFLOOR Slim
Composition |
|
Water, gypsum cellulose fibers |
nominal density |
Kg / m3 |
1150 ± 50 |
Maximum concentrated load allowed |
kN |
1 |
Maximum permissible distributed load |
kN |
2 |
Thermal conductivity |
0,32 |
W / mK |
Reaction to fire |
DM 26 / 06 / 84 |
Class 0 |
Thickness |
% |
<2 |
Binder-free, certified for green building |
|
|
Dimensional
ECOFLOOR Slim L - pipe spacing 100 m
 |
ECOFLOOR Slim B10 - pipe spacing 100 mm  |
ECOFLOOR Slim B5 - pipe spacing 50 m
 |
ECOFLOOR Slim C - collector area |
The collector in radiant systems is placed in the central area.
The direction of installation of the panels must follow the project of radiant circuits; the ECOFLOOR of Slim pipe spacing is fixed at 10 cm. The milling with linear panels, ECOFLOOR Slim L must be used in all areas in which the tube has a linear development; in the presence of curves need the rusticated B10 panels.
The rusticated B5 panels are used in the vicinity of the collector, adjacent to ECOFLOOR C panels, and in passageways such as corridors and lobbies.

system heating capacity
thermal performance data calculated with numerical simulations according to EN 15377. flow temperatures UNI EN 1264.
Contour conditions |
- Ambient temperature 20 ° C - Thermal gradient 5 ° C - Step installation 10 cm |
TW TS Q Qdown |
Flow temperature Surface temperature * thermal efficiency Dispersions down |
* The surface temperatures are rounded inside closer.

boundary temperature 20 ° C - total thermal resistance of the underlying elements of R = 1,8 2 m K / Watt heat transfer coefficients α according to UNI EN 1264-5
in cooling system made
thermal performance data calculated with numerical simulations according to EN 15377. flow temperatures UNI EN 1264.
Conditions contarno |
- Ambient temperature 26 ° C - Thermal gradient 5 ° C - Step installation 10 cm |
TW TS Q |
Flow temperature Surface temperature * cooling capacity |
The surface temperatures are rounded inside closer.

According to UNI EN 1264 the cooling flow temperature must not be lower by more than 1K to the value of the dew point temperature calculated for the ambient conditions. (Example ambient temperature of 26 ° C, relative humidity 50%: the dew point temperature is of 14,8 ° C and the outlet temperature may not be less than 13.8 ° C)
Components
PE-RT pipe
The pipe crossed by the heat transfer fluid is a key component of a heating system with radiant panels.
It must respond to numerous and stringent quality parameters to ensure good performance and long life: high levels of stress resistance of different nature must be guaranteed for at least 50 years with excellent safety margins.
The PE-RT pipe is a plastic pipe ideal for radiant surface systems, made with a special PE-RT resistant to high temperatures in compliance with Din 16833, in ethylene-octane copolymer.

The polymer structure is presented as a linear chain (ethylene) and the side chains of octane, producing a very durable material with excellent flexibility and durability.
The small diameter of the pipe in PE-RT, 12 mm, is ideal for its housing inside the milling of ECOFLOOR Slim panels and laying with small radii of curvature of the typical system. The limit in the development in length of the small diameter tube with circuits is exceeded with special Y-adapters that, in dividing the flow, do correspond to a single outlet to the manifold two radiating circuits.
ADVANTAGES
- Water resistant to oxygen;
- Small diameter ideal for low-thickness systems;
- High resistance to stess and injuries;
- Laying with small radii of curvature;
- Stability to thermal aging;
- Resistance to chemical solvents diluted in convector fluid;
- High resistance to corrosion;
- Smooth walls with minimal pressure losses and absence of fouling;
- Good resistance to the spread of lesions and resistance to abrasion.

distribution manifold
Collector newly designed for radiant floor systems, wall and ceiling heating and cooling. The number of outputs is variable from a minimum to a maximum of 2 18 and the installation can be both horizontal and vertical: the result is the perfect compatibility of the collector with any of the radiating system.
The preparation of the thermostatic control and the flow display are some of the manifold accessories that allow the perfect collector compatibility with any radiant system.
The preparation of the thermostatic control and the flow display are some of the manifold accessories designed to perfect the radiant system calibration and its subsequent and optimal steady state operation.
Flow Module
The supply module is equipped with flow meters and flow control valves incorporated. By means of the regulating valve the flow rate to the individual circuits can be precisely adjusted to the desired value, the value read directly on the scale of the single flow meter.
In this way it simplifies and speeds up the calibration operation of the circuit, without the need for reference graphs. The valve makes it possible to seal off the single circuit, in case of need.
return form
The return module is equipped with shut-off valves incorporated. By means of the shut-off valve with manual knob, the scope for the individual circuits can be reduced up to the complete closure of the same circuit.
The valves are designed for the application of an electric actuator, to make automatic on signal of a room thermostat.
Deposit port manifold
The cassette for accommodation of distribution collectors is the built-in type, designed to easily position the collectors of radiant systems.
ADVANTAGES
- Recessed box with galvanized sheet metal body
- Electro Network for paintable parts
- Rails for fast mounting manifolds
- Height-adjustable feet
- Frame and white door
- Easy positioning of the collector
Fittings Y-connection
By means of a special Y-joint it is possible to make two radiant circuits correspond to each output to the manifold: the joint has the function of dividing the flow rate over two circuits.
The use of joints allows to reduce installation costs and at the same time the dimensions of the manifold, while maintaining the functionality of the system.

The junction fittings are equipped with a bayonet terminal for connection to the pipe, according to a patented system.
The mechanical seal by means of tweezers positioned on the double O-ring ensures that the tube is not damaged.
The fluidic seal is guaranteed by the action of the double O-ring and the tube guide which maintains the circularity even in the presence of lateral loads.
In the event of checks or modifications to the system, the simple and univocal bayonet system allows considerable ease of disconnection.
- Ease of tube insertion
- No damage to the pipe
- Sealing Warranty fluidic
- Ease of disconnection.
Banda perimeter
The perimeter insulation tape is made of closed cell polyethylene, light raincoat, not decomposable and resistant to mold and high resistance to chemical attack and to alkaline reactions of concrete products.
The product is stable over time thanks to the compounds made by the extrusion of the polyethylene and the use of special glues. Both the polyethylene as the glues used are resistant to thermal shock.
The tape is ideal for the realization of underfloor heating-cooling.
Its position between the screed and all the structural elements with which it adjoins allows to absorb the expansion of the screed and to obtain a good thermal and acoustic insulation.